Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 382/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Electronic Circuit Breakers | |||||
Model | DAM1-1600 | ||||
Breaking Capacity Code | S | H | G | ||
Rated Current of Frame size- Inm (A) | 1600A | ||||
Rated Current-In(40,50 or 55ºC) (A) | 800 -1000 - 1250 - 1600A | ||||
Rated İnsulation Voltage -Ui(a.c.) 50-60Hz (V) | 750V | ||||
Rated operation Voltage -Ue(a.c.) 50-60Hz (V) | 400V | ||||
Number of Pole | 3P | ||||
Rated ultimate short Circuit breaking Capacity kA Icu AC400V/50Hz O-CO (KA) | 65 | 85 | 100 | ||
Rated service short Circuit breaking Capacity kA Ics AC400V/50Hz O-CO-CO (KA) | 50 | 50 | 50 | ||
Rated short-circuit breaking capacity Icm(peak)/cos ф AC400V/50HZ O-CO (KA) | 105/0.25 | 143/0.2 | 220/0.2 | ||
Rated impulse withstand Voltage -Uimp (V) | 8000 | ||||
Dielectric Propery (V) | 3000 | ||||
lonization distance (mm) | ≤80/0 | ||||
Endurance | Total Cycles | 3000 | |||
Electrical Life | 500 | ||||
Mechanical Life | 2500 | ||||
Over Current trip | Thermal release adjustable | (0,4-0,5-0,6-0,7-0,8-0,9-1)x1In | |||
Magnetic release adjustable | (1,5-2-4-6-8-10-12)xIn | ||||
Operating Curve at 6Ir | 3S-6S-12S-18S | ||||
Category (EN 60947-2/IEC 60947-2) | Main circuit | A/B | |||
Auxiliary circuit | AC-15 | ||||
Under Voltage Release | √ | ||||
Shunt Release | √ | ||||
Auxiliary Contact | √ | ||||
Alarm Contact | √ | ||||
Auxiliary Contact and Alarm Contact | √ | ||||
Handle Operation Mechanism | √ | ||||
Electrical Operastion Mechanism | √ | ||||
DIN clips | - | ||||
Terminal cover | √ | ||||
Phase seperator | √ | ||||
Extention Handle | √ | ||||
W (mm) | 3P | 210 | |||
4P | - | ||||
L (mm) | 3P | 406 | |||
4P | - | ||||
H (mm) | 3P | 138.5 | |||
4P | - | ||||
Weight | Fixed version 3P/4P | 17.2/22.2 | |||
Plug-in version 3P/4P | - | ||||
Draw out version 3P/4P | 22/30.1 |
Table1 PR211 type | ||||||||||||||
S.No. | Function | Settings | Type | PR211 | PR211 | PR211 | PR211 | Factroy reset | ||||||
Poles | 3P | 3P | 3P | 3P | ||||||||||
Rating (A) | 250 | 400 | 800 | 1600 | ||||||||||
1 | L | Overload Current Setting (A) | (0.4,0.5,0.6,0.7,0.8,0.9,0.95,1.0)xIn | (0.4,0.5,0.6,0.7,0.8,0.9,0.95,1.0)xIn | (0.4,0.5,0.6,0.7,0.8,0.9,0.95,1.0)xIn | (0.4,0.5,0.6,0.7,0.8,0.9,0.95,1.0)xIn | 1.0In | |||||||
2 | Time Delay at Overload Current Setting | 3S,6S,12S,18S | 3S,6S,12S,18S | 3S,6S,12S,18S | 3S,6S,12S,18S | 3S | ||||||||
3 | I | Instantaneous Current Setting | (1.5, 2, 4, 6, 8, 10, 12,OFF)xIn | (1.5, 2, 4, 6, 8, 10, 12,OFF)xIn | (1.5, 2, 4, 6, 8, 10, 12,OFF)xIn | (1.5, 2, 4, 6, 8, 10, 12,OFF)xIn | 10In | |||||||
Table2 PR212 type | ||||||||||||||
S.No. | Function | Settings | Type | PR212 | PR212 | PR212 | PR212 | Factroy reset | ||||||
Poles | 3P | 3P | 3P | 3P | ||||||||||
Rating (A) | 250 | 400/630 | 800 | 1600 | ||||||||||
1 | L | Overload Current Setting (A) | (0.4,0.5,0.55,0.6,0.65,0.7,0.75,0.8)xIn | (0.4,0.5,0.55,0.6,0.65,0.7,0.75,0.8)xIn | (0.4,0.5,0.55,0.6,0.65,0.7,0.75,0.8)xIn | (0.4,0.5,0.55,0.6,0.65,0.7,0.75,0.8)xIn | 1.0In | |||||||
2 | Time Delay at Overload Current Setting | 3S,6S,12S,18S | 3S,6S,12S,18S | 3S,6S,12S,18S | 3S,6S,12S,18S | 3S | ||||||||
3 | S | Short - Circuit Current Setting (A) | (1, 2, 3, 4, 6, 8, 10,OFF)xIn | (1, 2, 3, 4, 6, 8, 10,OFF)xIn | (1, 2, 3, 4, 6, 8, 10,OFF)xIn | (1, 2, 3, 4, 6, 8, 10,OFF)xIn | 6In | |||||||
4 | Time Delay at Short Circuit Current Setting | 0.05, 0.1, 0.25, 0.5 | 0.05, 0.1, 0.25, 0.5 | 0.05, 0.1, 0.25, 0.5 | 0.05, 0.1, 0.25, 0.5 | 0.1S | ||||||||
5 | I | Instantaneous Current Setting | (1.5, 2, 4, 6, 8, 10, 12,OFF)xIn | (1.5, 2, 4, 6, 8, 10, 12,OFF)xIn | (1.5, 2, 4, 6, 8, 10, 12,OFF)xIn | (1.5, 2, 4, 6, 8, 10, 12,OFF)xIn | 10In | |||||||
6 | G | Ground Fault Current Setting (A) | (0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn | (0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn | (0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn | (0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn | 1.0In | |||||||
7 | Time Delay at Ground Fault Setting | 0.1, 0.2, 0.4, 0.8 | 0.1, 0.2, 0.4, 0.8 | 0.1, 0.2, 0.4, 0.8 | 0.1, 0.2, 0.4, 0.8 | 0.4S | ||||||||
8 | Selection of electric or electronic parameters set | Function SET (switch ELT/MAN) | ||||||||||||
9 | Used for setting parameters of dip switch of zero line | InN=%In,switch 50/100 | ||||||||||||
10 | Socket for connection measuring device | Panel socket |