The DAM3 series marks a significant advancement over the DAM1 series, offering a reduced volume for space efficiency, enhanced breaking capacity for superior performance, and notable energy savings for cost-effective operation.
Electrical parameters of DAM3-250 molded case circuit breakerRated current of frame size Inm [A] | 250 | ||||
Rated current [A] | 100-250 | 100-225 | |||
Number of poles | 2 / 3 / 4 | ||||
Rated operating voltage | (AC)50-60HZ [V] | 400/690 | |||
DC [V] | 250/1000 | ||||
Rated impulse withstand voltage Uimp [KV] | 8 | ||||
Rated insulation voltage Ui [V] | 750 | ||||
Test voltage at industrial frequency for 1 min [V] | 3000 | ||||
Rated ultimate short-circuit breaking capacity Icu [KA] | B | C | N | S | |
(AC)50-60HZ 220/230V [KA] | 30 | 36 | 50 | 75 | |
(AC)50-60HZ 400/415V [KA] | 18 | 25 | 36 | 50 | |
(AC)50-60HZ 690V [KA] | 6 | 8 | 12 | 15 | |
(DC)250V-2 Poles in series | 18 | 22 | 30 | 40 | |
(DC)500V-2 Poles in series | 9 | 12 | 15 | 20 | |
(DC)750V-4 Poles in series | 16 | 18 | 22 | 30 | |
(DC)1000V-4 Poles in series | 13 | 15 | 18 | 25 | |
Rated service short-circuit breaking capacity, Ics [KA] | |||||
(AC)50-60HZ 220/230V [%Icu] | 60% | 60% | 60% | 50% | |
(AC)50-60HZ 400/415V [%Icu] | 60% | 60% | 60% | 50% | |
(AC)50-60HZ 690V [%Icu] | 60% | 60% | 60% | 50% | |
category of utilization (EN 60947-2) | A | ||||
Isolation condition | Bitmap | ||||
Reference standard | IEC/EN 60947-2/GB 14048.2 | ||||
Interchangeability | Bitmap | ||||
Versions | Fixed | Bitmap | |||
Plug-in | Bitmap | ||||
Draw-out | - |
Endurance | Total cycles | 10000 | |
Electrical endurance | 1500 | ||
Mechanical endurance | 8500 | ||
Basic dimensions-fixed version |
3/4 Poies W[mm] | 70(2P) /104 /139 | |
3/4 Poies H[mm] | 59 | 62.5 | |
H1[mm] | 78.5 | 82 | |
3/4 Poies L[mm] | 139 |
Introduction
The innovative DAM3-250 molded case circuit breaker is engineered to automatically disconnect the current when it surpasses the release setting, ensuring optimal safety. The term 'molded case' refers to the robust plastic insulator that forms the device's frame, effectively insulating the conductor and the metal grounding component.
Working principle
The DAM3-250 molded case circuit breaker features a main contact that can be manually manipulated or electrically closed. Once the main contact is secured, the free release mechanism locks it in the closed position. The overcurrent trip coil and thermal trip element are serially connected with the main circuit, while the undervoltage trip coil is arranged in parallel with the power supply, ensuring comprehensive protection and reliability.