Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 299/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Overview
Introducing the unparalleled Dada DAM3-1600 Molded Case Circuit Breaker, a powerhouse of protection with a formidable rated current capacity soaring up to 1600A. These exceptional devices are expertly crafted for safeguarding power distribution circuits operating at an alternating current of 50-60Hz, with rated operational currents reaching up to 1000A. Furthermore, these breakers are ideal for electric motors, offering not only infrequent starting capability but also robust overload protection. They stand as a vigilant shield against short circuiting and undervoltage threats, ensuring complete peace of mind.
The DAM3 series stands as a testament to innovation, delivering a marked improvement over the DAM1 series. With a more compact design and significantly higher breaking capacity, these breakers offer superior energy efficiency, making them a smarter choice for modern electrical systems.
Electrical parameters of DAM3-1600 molded case circuit breakerRated current of frame size Inm [A] | 1600 | |||
Rated current [A] | 1000 1250 1600 | |||
Number of poles | 3 / 4 | |||
Rated operating voltage | (AC)50-60HZ [V] | 400/690 | ||
DC [V] | 250/1000 | |||
Rated impulse withstand voltage Uimp [KV] | 8 | |||
Rated insulation voltage Ui[V] | 750 | |||
Test voltage at industrial frequency for 1 min [V] | 3000 | |||
Rated ultimate short-circuit breaking capacity Icu [KA] | S | H | G | |
(AC)50-60HZ 220/230V [KA] | 80 | 105 | 130 | |
(AC)50-60HZ 400/415V [KA] | 55 | 70 | 100 | |
(AC)50-60HZ 690V[KA] | 20 | 25 | 30 | |
(DC)250V-2 Poles in series | 50 | 65 | 80 | |
(DC)500V-2 Poles in series | 22 | 30 | 40 | |
(DC)750V-4 Poles in series | 42 | 55 | 68 | |
(DC)1000V-4 Poles in series | 35 | 45 | 55 | |
Rated service short-circuit breaking capacity, Ics [KA] | ||||
(AC)50-60HZ 220/230V [%Icu] | 60% | 60% | 60% | |
(AC)50-60HZ 400/415V [%Icu] | 60% | 60% | 60% | |
(AC)50-60HZ 690V[%Icu] | 60% | 60% | 60% | |
Category of utilisation(EN 60947-2) | A | |||
Isolation condition | Bitmap | |||
Reference standard | IEC/EN 60947-2/GB 14048.2 | |||
Interchangeability | Bitmap | |||
Versions | Fixed | Bitmap | ||
Plug-in | Bitmap | |||
Draw-out | Bitmap |
Endurance | Total cycles | 5000 |
Electrical endurance | 1000 | |
Mechanical endurance | 4000 | |
Basic dimensjons-fixed version |
3/4 Poies W[mm] | 210/280 |
3/4 Poies H[mm] | 140 | |
H1[mm] | 196 | |
3/4 Poies L[mm] | 328 |
Introduction
The DAM3-1600 Molded Case Circuit Breaker is engineered to automatically sever the current flow when it surpasses the release setting, ensuring safety and reliability. The term 'molded case' refers to the robust plastic insulator that forms the framework of this device, acting as a barrier to insulate the conductor and the metal grounding component, thereby enhancing operational safety.
Working principle
The operational brilliance of the DAM3-1600 Molded Case Circuit Breaker lies in its intricate mechanism. The main contact can be deftly controlled manually or electrically closed. Once the main contact achieves closure, the ingenious free release mechanism secures it firmly in the closed position. The system intricately connects the overcurrent trip coil and the thermal trip element in series with the main circuit, while the undervoltage trip coil and power supply are wired in parallel, ensuring seamless and efficient protection.