Customization: | Available |
---|---|
Type: | Power |
Structure: | Protection |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Name | Describe |
A | Photovoltaic array |
B. | Photovoltaic confluence box |
C | Grid-inverter |
D | Public power grid |
E | Environmental detector |
F | Data collector |
Type | L | L1 | L2 | W1 | W2 | H | H1 |
SCR-6/8 | 400 | 433 | 470 | 340 | 400 | 190.70 | 213.70 |
SCR-6/8M | 430 | 465 | 494 | 440 | 500 | 190 | 213 |
SDR-6/8 | 420 | 455 | 484 | 410 | 480 | 190.70 | 217.70 |
SDR-6/8M | 500 | 535 | 567 | 480 | 550 | 190.70 | 225 |
SCR-10/12 | 500 | 534 | 564 | 340 | 400 | 190 | 214 |
SCR-10/12M | 480 | 515 | 543 | 440 | 500 | 190.70 | 213.70 |
SDR-10/12M | 469 | 505 | 536 | 420 | 480 | 190.70 | 223.70 |
SDR-10/12M | 540 | 570 | 602 | 485 | 550 | 192 | 225 |
SCR-14/16 | 550 | 589.5 | 620 | 340 | 400 | 190 | 214 |
SDR-14/16M | 550 | 585 | 615 | 440 | 500 | 190 | 213 |
SDR-14/16 | 599 | 630 | 662 | 415 | 500 | 190 | 213 |
SDR-14/16M | 620 | 650 | 682 | 465 | 550 | 186 | 225 |
SCR-18 | 600 | 639 | 670 | 340 | 400 | 190.70 | 213.70 |
SCR-18M | 620 | 650 | 681 | 440 | 500 | 190.70 | 213.70 |
SCR-18 | 629 | 660 | 692 | 415 | 500 | 190.70 | 224.70 |
SCR-18M | 669 | 700 | 732 | 465 | 550 | 190.70 | 229.70 |
Unit: mm |
Part number | Explain : |
1 | Pv positive input insurance and fuse box |
2 | Pv negative input insurance and fuse box |
3 | Sampling board, auxiliary power supply board (non-intelligent without) |
4 | Lightning arrest 5 |
5 | Short - circuiter |
6 | Monitoring board (non-intelligent confluence box is not) 7 |
7 | Power grid ground wire terminal block |
8 | RS485 communication terminal (non-intelligent junction box is not) |
Terminal Description | Terminal specifications | Widing recommendation |
DC positive input (PV + IN) | PG7 | 4mm2 |
DC negative input (PV - IN) | PG7 | 4mm2 |
DC positive confluence input (PV + ) | PG 21 | 70mm2 |
DC negative confluence input (PV - ) | PG 21 | 70mm2 |
Grounding terminal | PG11. | 16mm2 |
Communication terminal | PG7 | 1.5mm2 Low resistance shielding double Twist Thread |
Terminal Description | Terminal specifications | Widing recommendation |
DC positive input (PV+IN) | PG7 | 4mm2 |
DC negative input (PV-IN) | PG7 | 4mm2 |
DC positive confluence input (PV+) | PG 21 | 70 mm2 |
DC negative confluence input (PV - ) | PG 21 | 70 mm2 |
Grounding terminal | PG11. | 16mm2 |
Communication terminal | PG7 | 1.5mm2 Low resistance shielding double Twist Thread |
Project | Number of pages | Display content |
6/8 Road Intelligent convergence with |
1-8 | PV DC input 1-8 channel current value (unit A) |
9-16 | Show " " | |
17 | PV voltage value (unit) | |
18 | Temperature in the box (unitºC) (The anti-reverse convergence box defaults to the radiator temperature) | |
19 | RS 485 communication address | |
20 | Type of confluence box machine | |
Project | Number of pages | Display content |
Route 10 Intelligent convergence with |
1 - 10 | PV DC input 1~10 channel current value (unit A) |
11-16 | Show" " | |
17 | PV voltage value (unit V) | |
18 | Temperature in the box (unit "C") (the default of the anti-reverse confluence box is the radiator temperature) | |
19 | RS485 communication address | |
20 | Confluence box machine type display | |
Project | Number of pages | Display content |
Route 12 Intelligent confluence box |
1-12 | PV DC input 1-8 channel current value (unit A) |
13 - 16 | Show "--" | |
17 | PV voltage value (unit) | |
18 | Temperature in the box (unit "C") (the default of the anti-reverse confluence box is the radiator temperature) | |
19 | RS 485 communication address | |
20 | Type of confluence box machine | |
Project | Number of pages | Display content |
Route 14/16 Intelligent confluence box |
1-16 | PV DC input 1~16 channel current value (unit A) |
17 | PV voltage value (unit) | |
18 | Temperature in the box (unit °C) (the default temperature of the anti-reverse convergence box is the radiator temperature) | |
19 | RS485 communication address | |
20 | Type of confluence box machine | |
Project | Number of pages | Display content |
Route 18 Intelligent confluence box |
1 - 19 | PV DC input 1~18 channel current value (unit A) |
19 | PV voltage value (unit) | |
20 | Temperature in the box (unit "C") (the default of the anti-reverse confluence box is the radiator temperature) | |
21 | RS485 communication address | |
22 | Type of confluence box machine |
Type | Dial code switch 1 | Dial code switch Two | Dial code switch Three |
6/8 Road | 1 | 0 | 0 |
Route 10 | 0 | 1 | 0 |
Route 12 | 1 | 1 | 0 |
Route 14/16 | 0 | 0 | 0 |
Route 18 | 1 | 0 | 1 |
Parameter Type |
SCRSDR-6M | SCRSDR-8 M | SCRSDR-10M | SCRSDR-12M | SCRSDR-14M | SCRSDR-16M | SCRSDR-18M |
The maximum current input for each channel | 9.6A | 9.6A | 9.6A | 9.6A | 9.6A | 9.6A | 9.6A |
Communication method | RS 485 | RS 485 | RS 485 | RS 485 | RS 485 | RS 485 | RS 485 |
PV input maximum voltage | 1000V | 1000V | 1000V | 1000V | 1000V | 1000V | 1000V |
The maximum number of connectible components | 6 | 8 | 10 | 12 | 14 | 16 | 18 |
Waterproof level | IP65 | IP65 | IP65 | IP65 | IP65 | IP65 | IP65 |
Ambient temperature | -25°C-55°C | ||||||
Environmental humidity | 0~99% | ||||||
DC total output circuit breaker | Have | ||||||
Special lightning protection module for photovoltaics Have | Have | ||||||
Photovoltaic array current monitoring | Have | ||||||
Lightning arrator failure monitoring | Have | ||||||
Short-circuit failure monitoring | Have | ||||||
Communication interface | RS 485 |
Parameter Type |
SCRSDR-6M | SCRSDR-8 M | SCRSDR-10M | SCRSDR-12M | SCRSDR-14M | SCRSDR-16M | SCRSDR-18M |
The maximum current input for each channel | 9.6A | 9.6A | 9.6A | 9.6A | 9.6A | 9.6A | 9.6A |
Communication method | RS 485 | RS 485 | RS 485 | RS 485 | RS 485 | RS 485 | RS 485 |
PV input maximum voltage | 1000V | 1000V | 1000V | 1000V | 1000V | 1000V | 1000V |
The maximum number of connectible components | 6 | 8 | 10 | 12 | 14 | 16 | 18 |
Waterproof level | IP65 | IP65 | IP65 | IP65 | IP65 | IP65 | IP65 |
Ambient temperature | -25°C-55°C | ||||||
Environmental humidity | 0~99% | ||||||
DC total output circuit breaker | Not have | ||||||
Special lightning protection module for photovoltaics | Not have | ||||||
Photovoltaic array current monitoring | Not have | ||||||
Lightning arrator failure monitoring | Not have | ||||||
Short-circuit failure monitoring | Not have | ||||||
Communication interface | Not have |