Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCB

Product Details
Customization: Available
Breaking Capacity: Low Voltage Circuit Breakers
Operation: Manual Type
Still deciding? Get samples of US$ 10/Piece
Request Sample
Manufacturer/Factory

360° Virtual Tour

Diamond Member Since 2020

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
Cooperated with Fortune 500
This supplier has Cooperated with Fortune 500 companies
Years of Export Experience
The export experience of the supplier is more than 10 years
Exhibition Experience
The supplier had participated in offline trade shows, you can check the Audit Report for more information
to see all verified strength labels (25)
  • Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCB
  • Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCB
  • Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCB
  • Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCB
  • Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCB
  • Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCB
Find Similar Products

Basic Info.

Model NO.
CM1-125
Arc-extinguishing Medium
Arc Chamber
Installation
Fixed
Structure
MCCB
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection
Transport Package
Carton
Specification
12.5, 16, 20, 25, 32, 40, 50, 70, 80, 100A
Trademark
CDADA, OEM, ODM
Origin
Shanghai, China
HS Code
85362000
Production Capacity
10000PCS/Month

Product Description

Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCB


The DAM2 series Moulded Case Circuit Breaker is a revolutionary product, crafted with precision using state-of-the-art international technology. These circuit breakers are designed to be compact yet powerful, offering outstanding breaking capacity and minimal arc-over distance. Their robust, shake-proof design makes them a top-tier choice for a wide range of applications, whether on land or at sea.

Application

The DAM2 (CM1) series circuit breaker is a pinnacle of engineering with a rated insulation voltage of 800V. It is meticulously crafted for AC distribution networks at 50Hz/60Hz, supporting a rated working voltage of up to 690V and a rated current of up to 1250A. This breaker is the ideal solution for power distribution and offers unmatched protection for circuits and equipment against overloads, short circuits, under-voltage, and various other faults. It also facilitates infrequent circuit conversions and motor starts. Its versatility allows for both vertical and horizontal installations, and it is suitable for isolation applications, as indicated by the symbol " ". The DAM2 MCCB meets the stringent IEC60947-2 standard for low-voltage switchgear and control equipment, ensuring reliability and safety.

Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCBFixed Type Switch 250A Moulded Case Breaker Dam2 MCCB

Normal operating conditions

1. Ambient air temperature: The breaker operates efficiently in temperatures ranging from -5ºC to +40ºC, with a daily average not surpassing +35ºC.
2. Altitude: The installation site should not exceed an altitude of 2000 meters to maintain optimal performance.
3. Atmospheric conditions: At a peak temperature of +40ºC, the relative humidity must not exceed 50%. Higher humidity levels are permissible at cooler temperatures. The average maximum relative humidity is 90%, with an average minimum monthly temperature of +25ºC, considering possible temperature variations that might lead to condensation on the product surface.
4. Pollution Degree: 3, ensuring the breaker can withstand challenging environmental conditions.

Selection of instructions

Classified by pole types:
Type A: N-pole without over-current release components remains continuously connected, operating independently from the other three poles.
Type B: N-pole without over-current release components functions harmoniously with the other three poles, activating before deactivation.
Type C: N-pole equipped with over-current release components, working in tandem with the other three poles, where N-pole activates prior to deactivation.

Classified by rated current of over-current release:
DAM2-63 MCCB available in nine ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63 A, offering flexibility and choice in various applications.
DAM2-100 MCCB available in nine ratings: 16, 20, 25, 32, 40, 50, 63, 80, 100 A, catering to a broad spectrum of electrical needs.
DAM2-250 MCCB available in seven ratings: 100, 125, 140, 160, 180, 200, 225, 250 A, designed for more demanding electrical systems.
DAM2-400 MCCB available in five ratings: 225, 250, 315, 350, 400 A, ensuring robust performance in larger installations.
DAM2-630 MCCB available in three ratings: 400, 500, 630 A, suitable for high-capacity systems.
DAM2-800 MCCB available in three ratings: 630, 700, 800 A, providing powerful options for substantial electrical demands.
DAM2-1250 MCCB available in three ratings: 800, 1000, 1250 A, tailored for the most intensive applications.
Remark: The 6A version is specifically designed for electromagnetic (instantaneous) type utilization. However, it is not recommended due to its specification limitations, ensuring optimal performance in other available versions.
Wiring Options: Tailor your installation needs with options including front-of-board wiring, back-of-board wiring, or insertion type wiring, providing exceptional versatility and seamless integration into various setups.
Over-Current Release Patterns: Experience flexibility with thermodynamic-electromagnetic (dual) type and electromagnetic (instantaneous) type, each catering excellently to diverse operational demands.
Outfit Options: Customize your setup with a choice between circuit breakers equipped with outfit or those without, aligning perfectly with your unique specifications and preferences.
Outfit Details: Enhance functionality with inner accessories like shunt release, under-voltage release, auxiliary contact, and alarm contact. Outer accessories boast convenience and reliability with turning handle operation mechanisms and power-driven operation mechanisms, among others.
Breaking Capacity: With options of L-standard, M-second high, and H-high breaking types, this variety meets the demands of a wide range of applications, ensuring robust performance every time.

Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCBFixed Type Switch 250A Moulded Case Breaker Dam2 MCCB


Technical Parameters

1. Instantaneous Action Characteristics: For distribution circuit breakers, enjoy a precise setting value of 10In±20%. Meanwhile, the DAM2-1250 model offers a reliable setting of 7In±20%. Motor protection circuit breakers are finely tuned with a setting value of 12In±20%.
2. Rated Values: For comprehensive details on the rated values of our circuit breakers, refer to Table 2.
3. Ambient Temperature: Evaluate performance with over-current release action characteristics at +40ºC, detailed in Table 3 for distribution circuit breakers and in Table 4 for motor protection circuit breakers.

Rated Value: Discover thorough specifications detailing the rated values, ensuring clarity and reliability in your circuit breaker's performance.

Model Pole Rated current (A) Rated
operating
voltage (V)
Rated
insulation
voltage (V)
Rated ultimate short - circuit breaking capacity (Icu) Flashover
distance(mm)
Test voltage (V) Icu (kA) Ics (kA)
DAM2L-63 3 10,16,20,25,
32,40,50,63
400 500 400×1.10 25 18 0
DAM2M-63 3,4 50 35
DAM2L-100 3,4 16,20,25,32,40,
50,63,80,100
400 800 30 22 ≤50
DAM2M-100 2,3,4 50 35
DAM2H-100 3 85 50
DAM2L-100 3,4 690 10 5
DAM2M-100 2,3,4 20 10
DAM2L-225 3,4 100,125,140,
160,180,200,225
400 800 35 25
TXCM1-225 2,3,4 50 35
DAM2H-225 3 85 50
DAM2L-225 3,4 690 10 5
DAM2M-225 2,3,4 20 10
DAM2L-400 3 225,250,315,
350,400
400 800 50 35 ≤100
DAM2M-400 3,4 65 42
DAM2H-400 3 100 65
DAM2L-400 3 690 15 8
DAM2M-400 3,4 20 10
DAM2L-630 3 400,500,630 400 800 50 35
DAM2M-630 3,4 65 42
DAM2H-630 3 100 65
DAM2L-630 3 6910 15 8
DAM2M-630 3,4 20 10
DAM2M-800 3 630,700,800 400 800 75 50
DAM2H-800 3 100 65
DAM2M-800 3 4690 30 15
DAM2-1250 3 800,1000,1250 400 800 85 42
DAM2-1250 3 690 25 12.5

Note: Both 2-pole and 4-pole circuit breakers, classified in L, M, and H types, offer a breaking index that matches the M-type, ensuring consistent performance across categories.

Inverse Time Breaking Action: Understand the robust characteristics of over-current release for power distribution scenarios when all poles are energized simultaneously.

No. Test current I/In Set time Initial state
1 Conventional non-tripping current 1.05 2h(In>63A),1h(In≤63A) Cold
2 Conventional non-tripping current 1.30 2h(In>63A),1h(In≤63A) Immediately after Test 1

Instantaneous Action Characteristics: Distribution circuit breakers are calibrated to a setting value of 10In±20%, while motor protection circuit breakers are optimized with a setting value of 12In±20%.

Inverse Time Breaking Action: Gain insights into the characteristics of over-current release for motor protection when all poles are simultaneously powered, ensuring efficiency and safety.

No. I/In Set time Initial state Remark
1 1.0 >2h Cold  
2 1.2 ≤2h Immediately after Test 1  
3 1.5 ≤4min Cold 10≤n≤225
≤8min 225 < in ≤ 630
4 7.2 4s≤T≤10s Cold 10≤In≤225
6s≤T≤20s 225 < in ≤ 630

Accessories

1. Internal Accessories of Circuit Breakers

1.1 Shunt Release
Shunt Release Voltage: The circuit breaker ensures reliable operation with a rated control supply voltage of AC50Hz, 230V, 400V; DC110V, 220V, 24V, functioning impeccably within a 70%~110% voltage range.

DC24V Shunt Release: Ensure reliable operation by adhering to specified copper wire length requirements, maintaining optimal performance.

Rated control
supply voltage Uc(DC24V)/Conductor area
1.5mm² 2.5mm²
100%Uc
85%Uc
150m
100m
250m
160m

Design Recommendations: Should table specifications not be met, design the shunt release control circuit following the provided figure to maintain operational integrity.

1.2 Under-Voltage Release

Under-Voltage Operation: With supply voltage dropping to 70%-35% of rated voltage, the under-voltage release ensures the circuit breaker's reliability and safety.
Under-Voltage Protection: Below 35% rated voltage, the under-voltage release prevents closure of the circuit breaker; above 85%, it ensures secure closure, safeguarding systems efficiently.
Closing Mechanism: Assure secure closure of the circuit breaker with the under-voltage release function at supply voltages exceeding 85% of the rated value.
Under-Voltage Ratings: Rated at AC50Hz, 230V, 400V, our circuit breakers promise reliable performance and unwavering security.
400V.
Special Note: Circuit breakers equipped with under-voltage release are expertly designed to operate correctly only at rated voltage, ensuring safe and efficient opening and closing mechanisms.
normally.

1.3 Pre-Paid Meter Dedicated Release

Step into a world of precision with our pre-paid meter dedicated release, boasting a rated operating voltage Ue of AC230/50Hz. This ensures exceptional performance across an extensive range of 65% to 110% of Ue. In an extraordinary display of safety and reliability, upon disengagement of the control (Ctrl), the circuit breaker is designed to execute a delayed opening within a span of 0.5 to 2 seconds.

Wiring Diagram for Pre-Paid Meter Dedicated Release

1.4 Rated Values of Auxiliary Contacts and Alarm Contacts (Refer to Table 5)

Classification Conventional thermal current (Ith) Rated current when

 

AC 400V Ie(AC-15)

Rated current when

 

DC 220V Ie(DC-13)

Auxiliary contact 3 0.4 0.15
Alarm contact 3 0.3 0.15

a. Auxiliary Contact: A comprehensive overview of its rated values and potential applications.

b. Alarm Contact: Discover the critical role and specifications of alarm contacts here.
Alarm contacts are meticulously engineered to remain inoperative during standard circuit breaker functions. They are designed to transition between normally open and normally closed states exclusively during free tripping or fault tripping, providing precise notifications only when necessary.

2. External Accessories for Circuit Breakers: Enhance functionality with our range of external accessories.

2.1 Motor Operating Mechanism: Explore the rated values and corresponding codes in detail within Table 6.

Category/Model DAM2-63. 125. 250 DAM2-400. 630. 800. 1250
Structure type Electromagnet Motor
AC voltage code AC50Hz,230V,400 AC50Hz,230V,400
DC voltage code DC110V,220V DC110V,220V

NOTE: After the circuit breaker trips with an electric operating mechanism, the mechanism must reset the circuit breaker before it can be closed again, ensuring readiness and efficiency.

Principle Diagram for Opening and Closing of DAM2-63,100,225 Electric Operating Mechanism (AC): Visualize the operational intricacies.

Principle Diagram for Opening and Closing of DAM2-400,630,800,1250 Electric Operating Mechanism (AC): Detailed insight into larger capacity models.

2.2 Installation Dimensions for Manual Operating Mechanism (Refer to Table 10): Accurate measurements for seamless installation.
Diagram of Handle Mounting Hole for DAM2-63~800: An essential guide for proper handle installation.

Total Height of Electric/Manual Operating Mechanism of Circuit Breaker (mm) (Refer to Table 12): Precise height specifications for informed installations.

Model Total height of electric
operating mechanism H
Installation dimensions

 

of manual operating mechanism H

DAM2L-63 155 49
DAM2M/H-63 164 49
DAM2L-100 152 51
DAM2M/H-100 170 51
DAM2L-225 182 54
DAM2M/H-225 199 54
DAM2L/M/H-400 255 88
DAM2M/H-630 262 89
DAM2M/H-800 261 96
DAM2H-1250 290 103

Quick Selection Table for DAM2 Series Molded Case Circuit Breakers: Simplify your choice with our comprehensive selection guide.

Corresponding
letters
Function name Function corresponding to the model
a Model features DAM2 Molded Case

 

Circuit Breaker

b Frame rated current code 63A,100A,225A,

 

400A,630A,800A,

1250A

c Breaking capacity characteristic
code
L-standard breaking type;

 

M-second high breaking type;

H-high breaking type

d Operation mode code No code for handle operation;

 

P for electric operation;

Z for turning handle operation

e Pole 2-two poles;

 

3-three poles;

4-four poles

f Release name 2 Electromagnetic release;

 

3 Double release

g Accessory 00 Without accessory
08 Alarm contact
10 Shunt release
20 Auxiliary contact
30 Undervoltage release
40 Shunt release, Auxiliary contact
50 Shunt release, Undervoltage release
60 Two sets of auxiliary contacts
70 Auxiliary contact, Undervoltage release
18 Shunt release, Alarm contact
28 Auxiliary contact, Alarm contact
38 Undervoltage release, Alarm contact
48 Shunt release, Auxiliary contact, Alarm contact
58 Shunt release, Undervoltage release, Alarm contact
68 Two sets of auxiliary contacts, Alarm contact
78 Auxiliary contact, Undervoltage release, Alarm contact
10Y Pre-paid meter dedicated release
40Y Pre-paid meter dedicated release, Auxiliary contact
50Y Pre-paid meter dedicated release, Auxiliary contact, Undervoltage release
18Y Pre-paid meter dedicated release, Alarm contact
48Y Pre-paid meter dedicated release, Auxiliary contact, Alarm contact
58Y Pre-paid meter dedicated release, Undervoltage release, Alarm contact
h Application No code for distribution;

 

2 for motor protection

i Conventional products No code;

 

T for transparent cover products

j Amperage 10,16,20,25,32,63,80,100,125,160,180,200
,225,250,315,350,400,500,630,700,800,1000
,1250

Example: DAM2L-100 / 33102 63A denotes a DAM2-type molded case circuit breaker with a framed current rating of 100A, standard breaking capacity, handle operation, 3 poles, double release, with shunt release, tailored for motor protection with a rated current of 63A.
Selection, installation, and usage must strictly adhere to the product manual or applicable national standards to ensure peak performance and safety.
Note: The N-pole type of a 4P circuit breaker is available in A-type and B-type. Without specific instructions, B-type is the default selection.

Working Principle: Uncover the foundational mechanics of our circuit breakers.
The main contact of the molded case circuit breaker can be actuated manually or electrically. Once engaged, the free release mechanism securely locks the main contact in place. The over
current trip coil and the thermal trip element are intricately connected in series with the main circuit, whereas the under
voltage
release
coil and the power supply are configured in parallel, ensuring robust performance and protection.
Fixed Type Switch 250A Moulded Case Breaker Dam2 MCCB

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier