The Dada DAM3-1600 molded case circuit breaker is an industry leader in electrical protection, featuring a formidable rated current capacity of up to 1600A. Crafted for supreme performance in protecting power distribution circuits, it operates flawlessly within an AC frequency range of 50-60Hz and supports a rated operating current up to 1000A. This versatile and durable device is engineered to deliver maximum safety for electric motors, providing dependable overload protection, occasional starting functions, and unparalleled defense against short circuits and undervoltage occurrences.
Setting the bar high, the DAM3 series elevates performance standards beyond its predecessor, the DAM1 series, by offering a more compact design combined with superior breaking capacity. Built for optimal efficiency, these circuit breakers are not only space-saving but also demonstrate extraordinary energy efficiency, establishing a new industry standard.
Electrical parameters of DAM3-1600 molded case circuit breakerRated current of frame size Inm [A] | 1600 | |||
Rated current [A] | 1000 1250 1600 | |||
Number of poles | 3 / 4 | |||
Rated operating voltage | (AC)50-60HZ [V] | 400/690 | ||
DC [V] | 250/1000 | |||
Rated impulse withstand voltage Uimp [KV] | 8 | |||
Rated insulation voltage Ui[V] | 750 | |||
Test voltage at industrial frequency for 1 min [V] | 3000 | |||
Rated ultimate short-circuit breaking capacity Icu [KA] | S | H | G | |
(AC)50-60HZ 220/230V [KA] | 80 | 105 | 130 | |
(AC)50-60HZ 400/415V [KA] | 55 | 70 | 100 | |
(AC)50-60HZ 690V[KA] | 20 | 25 | 30 | |
(DC)250V-2 Poles in series | 50 | 65 | 80 | |
(DC)500V-2 Poles in series | 22 | 30 | 40 | |
(DC)750V-4 Poles in series | 42 | 55 | 68 | |
(DC)1000V-4 Poles in series | 35 | 45 | 55 | |
Rated service short-circuit breaking capacity, Ics [KA] | ||||
(AC)50-60HZ 220/230V [%Icu] | 60% | 60% | 60% | |
(AC)50-60HZ 400/415V [%Icu] | 60% | 60% | 60% | |
(AC)50-60HZ 690V[%Icu] | 60% | 60% | 60% | |
Category of utilisation(EN 60947-2) | A | |||
Isolation condition | Bitmap | |||
Reference standard | IEC/EN 60947-2/GB 14048.2 | |||
Interchangeability | Bitmap | |||
Versions | Fixed | Bitmap | ||
Plug-in | Bitmap | |||
Draw-out | Bitmap |
Endurance | Total cycles | 5000 |
Electrical endurance | 1000 | |
Mechanical endurance | 4000 | |
Basic dimensjons-fixed version |
3/4 Poies W[mm] | 210/280 |
3/4 Poies H[mm] | 140 | |
H1[mm] | 196 | |
3/4 Poies L[mm] | 328 |
Introduction
The DAM3-1600 molded case circuit breaker is an advanced protective device designed to ensure user safety by automatically disconnecting power when the current exceeds its predetermined release threshold. This sophisticated system utilizes a molded case constructed from robust plastic insulators, which forms the enclosure of the device, effectively insulating the conductors and metal grounding elements to enhance safety.
Working principle
Functioning with exceptional accuracy, the DAM3-1600 molded case circuit breaker features a primary contact that can be manipulated manually or through an electric closure. Once locked in the closed position by the free release mechanism, the breaker is primed to protect. The overcurrent trip coil and thermal trip element, integrated in series with the main circuit, swiftly react to excess current, while the undervoltage trip coil, connected in parallel with the power source, ensures unwavering protection against voltage fluctuations.