Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 19/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The DAM3 series, an evolution from the DAM1 series, are engineered to deliver a more compact design, superior breaking capacity, and enhanced energy efficiency, setting new benchmarks in performance and sustainability.
Electrical parameters of the DAM3-250 molded case circuit breakerRated current of frame size Inm [A] | 250 | ||||
Rated current [A] | 100-250 | 100-225 | |||
Number of poles | 2 / 3 / 4 | ||||
Rated operating voltage | (AC)50-60HZ [V] | 400/690 | |||
DC [V] | 250/1000 | ||||
Rated impulse withstand voltage Uimp [KV] | 8 | ||||
Rated insulation voltage Ui [V] | 750 | ||||
Test voltage at industrial frequency for 1 min [V] | 3000 | ||||
Rated ultimate short-circuit breaking capacity Icu [KA] | B | C | N | S | |
(AC)50-60HZ 220/230V [KA] | 30 | 36 | 50 | 75 | |
(AC)50-60HZ 400/415V [KA] | 18 | 25 | 36 | 50 | |
(AC)50-60HZ 690V [KA] | 6 | 8 | 12 | 15 | |
(DC)250V-2 Poles in series | 18 | 22 | 30 | 40 | |
(DC)500V-2 Poles in series | 9 | 12 | 15 | 20 | |
(DC)750V-4 Poles in series | 16 | 18 | 22 | 30 | |
(DC)1000V-4 Poles in series | 13 | 15 | 18 | 25 | |
Rated service short-circuit breaking capacity, Ics [KA] | |||||
(AC)50-60HZ 220/230V [%Icu] | 60% | 60% | 60% | 50% | |
(AC)50-60HZ 400/415V [%Icu] | 60% | 60% | 60% | 50% | |
(AC)50-60HZ 690V [%Icu] | 60% | 60% | 60% | 50% | |
category of utilization (EN 60947-2) | A | ||||
Isolation condition | Bitmap | ||||
Reference standard | IEC/EN 60947-2/GB 14048.2 | ||||
Interchangeability | Bitmap | ||||
Versions | Fixed | Bitmap | |||
Plug-in | Bitmap | ||||
Draw-out | - |
Endurance | Total cycles | 10000 | |
Electrical endurance | 1500 | ||
Mechanical endurance | 8500 | ||
Basic dimensions-fixed version |
3/4 Poies W[mm] | 70(2P) /104 /139 | |
3/4 Poies H[mm] | 59 | 62.5 | |
H1[mm] | 78.5 | 82 | |
3/4 Poies L[mm] | 139 |
Introduction
The DAM3-250 molded case circuit breaker is designed to automatically interrupt the current flow when it surpasses the pre-set release threshold. The term 'molded case' refers to the robust plastic insulation frame that encloses the device, ensuring effective isolation of conductive parts and the metal grounding components.
Working principle
The main contact of the DAM3-250 molded case circuit breaker can be engaged either manually or electrically. Once closed, the free release mechanism securely locks the main contact in place. The overcurrent trip coil and thermal trip element are integrated in series with the main circuit, while the undervoltage trip coil is connected in parallel with the power supply, ensuring comprehensive protection and reliability.