Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 14/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Thermal-Magnetic fixed type Circuit Breakers | |||||
Model | DAM1-160 | ||||
Breaking Capacity Code | B | N | S | ||
Rated Current of Frame size- Inm (A) | 160A | ||||
Rated Current-In(40,50 or 55ºC) (A) | 10- 12,5-16-20 - 25 - 32 - 40 - 50 - 63 - 80 - 100 -125 - 160(150)A | ||||
Rated İnsulation Voltage -Ui(a.c.) 50-60Hz (V) | 750V | ||||
Rated operation Voltage -Ue(a.c.) 50-60Hz (V) | 400/415V | ||||
Number of Pole | 3P / 4P | ||||
Rated ultimate short Circuit breaking Capacity kA Icu AC400V/50Hz O-CO (KA) | 25 | 35 | 50 | ||
Rated service short Circuit breaking Capacity kA Ics AC400V/50Hz O-CO-CO (KA) | 12.5 | 26.25 | 37.5 | ||
Rated short-circuit breaking capacity Icm(peak)/cos ф AC400V/50HZ O-CO (KA) | 41/0.3 | 73.5/0.25 | 110/0.25 | ||
Rated impulse withstand Voltage -Uimp (V) | 8000 | ||||
Dielectric Propery (V) | 3000 | ||||
lonization distance (mm) | ≤30/0 | ||||
Endurance | Total Cycles | 8000 | |||
Electrical Life | 1000 | ||||
Mechanical Life | 7000 | ||||
Over Current trip | Thermal and Magnetic release fix type | √ | |||
Category (EN 60947-2/IEC 60947-2) | Main circuit | A/0 | |||
Auxiliary circuit | AC-15 | ||||
Under Voltage Release | √ | ||||
Shunt Release | √ | ||||
Auxiliary Contact | √ | ||||
Alarm Contact | √ | ||||
Auxiliary Contact and Alarm Contact | √ | ||||
Handle Operation Mechanism | √ | ||||
Electrical Operastion Mechanism | √ | ||||
DIN clips | √ | ||||
Terminal cover | √ | ||||
Phase seperator | √ | ||||
Extention Handle | - | ||||
W (mm) | 3P | 90 | |||
4P | 120 | ||||
L (mm) | 3P | 120 | |||
4P | 120 | ||||
H (mm) | 3P | 70 | |||
4P | 70 | ||||
Weight | Fixed version 3P/4P | 1.2/1.6 | |||
Plug-in version 3P/4P | 1.4/1.8 | ||||
Draw out version 3P/4P | - |