Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 299/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Overview
The Dada DAM3-1600 molded case circuit breaker boasts a robust rated current capacity of up to 1600A. Perfectly engineered for safeguarding power distribution circuits operating at an alternating current of 50-60Hz and rated operating currents up to 1000A, this versatile device also excels in electric motor applications for infrequent starts, overload protection, and defense against short circuits and undervoltage situations.
In comparison to the DAM1 series, our advanced DAM3 series is designed with a more compact form factor, enhanced breaking capacity, and superior energy efficiency, ensuring optimal performance and cost savings.
Electrical Parameters of DAM3-1600 Molded Case Circuit BreakerRated current of frame size Inm [A] | 1600 | |||
Rated current [A] | 1000 1250 1600 | |||
Number of poles | 3 / 4 | |||
Rated operating voltage | (AC)50-60HZ [V] | 400/690 | ||
DC [V] | 250/1000 | |||
Rated impulse withstand voltage Uimp [KV] | 8 | |||
Rated insulation voltage Ui[V] | 750 | |||
Test voltage at industrial frequency for 1 min [V] | 3000 | |||
Rated ultimate short-circuit breaking capacity Icu [KA] | S | H | G | |
(AC)50-60HZ 220/230V [KA] | 80 | 105 | 130 | |
(AC)50-60HZ 400/415V [KA] | 55 | 70 | 100 | |
(AC)50-60HZ 690V[KA] | 20 | 25 | 30 | |
(DC)250V-2 Poles in series | 50 | 65 | 80 | |
(DC)500V-2 Poles in series | 22 | 30 | 40 | |
(DC)750V-4 Poles in series | 42 | 55 | 68 | |
(DC)1000V-4 Poles in series | 35 | 45 | 55 | |
Rated service short-circuit breaking capacity, Ics [KA] | ||||
(AC)50-60HZ 220/230V [%Icu] | 60% | 60% | 60% | |
(AC)50-60HZ 400/415V [%Icu] | 60% | 60% | 60% | |
(AC)50-60HZ 690V[%Icu] | 60% | 60% | 60% | |
Category of utilisation(EN 60947-2) | A | |||
Isolation condition | Bitmap | |||
Reference standard | IEC/EN 60947-2/GB 14048.2 | |||
Interchangeability | Bitmap | |||
Versions | Fixed | Bitmap | ||
Plug-in | Bitmap | |||
Draw-out | Bitmap |
Endurance | Total cycles | 5000 |
Electrical endurance | 1000 | |
Mechanical endurance | 4000 | |
Basic dimensjons-fixed version |
3/4 Poies W[mm] | 210/280 |
3/4 Poies H[mm] | 140 | |
H1[mm] | 196 | |
3/4 Poies L[mm] | 328 |
Introduction
The DAM3-1600 molded case circuit breaker is engineered to automatically interrupt the current flow when it surpasses the preset release setting. The term 'molded case' refers to the high-grade plastic insulator encasing the device, which efficiently isolates the conductor from the metal grounding component.
Working Principle
The primary contact of the DAM3-1600 molded case circuit breaker can be manipulated manually or electrically to close the circuit. Upon closure, the free-release mechanism secures the main contact in the closed position. The overcurrent trip coil and thermal trip element are serially linked with the main circuit, while the undervoltage trip coil operates in parallel with the power supply, providing a comprehensive protection mechanism.