ALF-63N/H Series Miniature Circuit Breaker | |
Standard | EN/IEC60898-1 |
Breaking capacity(kA) | 6,10 |
Protection | Against overload and short circuit |
Rated current(A)In | 1,2,3,4,6,10,13,16,20,25,32,40,50,63 |
Rated voltage(V) | 1PAC 230/400,240/415 |
1P+N,2P,3P,3P+N,4PAC400/415 | |
Rated impulse withstand voltage Uimp(kV) | 4 |
Rated insulation voltage Ui(V) | 500 |
Energy limiting cass | 3 |
Ambient temperature(ºC) | -25~+40,Max.95%humidity |
Thermal operating limit | 1.13xln No tripping within an hour |
1.45xIn Tripping within an hour | |
Magnertic operating | B:(3-5)xIn,C:(5-10)xIn,D:(10-20)xIn |
Number of poles | 1P,1P+N,2P,3P,3P+N and 4P |
Type of trip | Thermal/magnetic release |
Terminal capacity | 16mm² flexible or 25mm² rigid up to 25A ratings |
25mm²flexible or 35mm²rigid from 32A to 63A ratings | |
Protection degree | IP20 |
Installation | Mounting on 35mm DIN rail |
Width | 17.8mm per pole |
NO. | Rated current of release(A) | Initial state | Test current | Specified time | Result to be obtained | Remarks |
1 | 1-63 | cold state | 1.13In | t≤1h | Non-trip | |
2 | 1-63 | upon the previous test | 1.45ln | t<1h | trip | Setting current up to specified value steadily in 5s |
3 | In≤32 | cold state | 2.55In | 1s<t<60s 1s<t<120s | trip | |
In>32 | ||||||
4 | 1-63 | cold state | 3In | t≤0.1s | Non-trip | B type |
5In | t<0.1s | trip | B type | |||
5In 10ln | t≤0.1s | Non-trip | C type | |||
10In | t<0.1s | trip | C type | |||
20ln | t≤0.1s | Non-trip | D type | |||
t<0.1s | trip | D type |
Category | Operation Cycles | Operation frequency | Rated current |
Electrical endurance | 4000 | 240/h | 1-32 |
120/h | 40-63 | ||
Mechanical endurance | 10000 | 240/h | 1-63 |