| Table1 PR211 type |
| S.No. |
Function |
Settings |
Type |
PR211 |
PR211 |
PR211 |
PR211 |
Factroy reset |
| Poles |
3P |
3P |
3P |
3P |
| Rating (A) |
250 |
400 |
800 |
1600 |
| 1 |
L |
Overload Current Setting (A) |
(0.4,0.5,0.6,0.7,0.8,0.9,0.95,1.0)xIn |
(0.4,0.5,0.6,0.7,0.8,0.9,0.95,1.0)xIn |
(0.4,0.5,0.6,0.7,0.8,0.9,0.95,1.0)xIn |
(0.4,0.5,0.6,0.7,0.8,0.9,0.95,1.0)xIn |
1.0In |
| 2 |
Time Delay at Overload Current Setting |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S |
| 3 |
I |
Instantaneous Current Setting |
(1.5, 2, 4, 6, 8, 10, 12,OFF)xIn |
(1.5, 2, 4, 6, 8, 10, 12,OFF)xIn |
(1.5, 2, 4, 6, 8, 10, 12,OFF)xIn |
(1.5, 2, 4, 6, 8, 10, 12,OFF)xIn |
10In |
| Table2 PR212 type |
| S.No. |
Function |
Settings |
Type |
PR212 |
PR212 |
PR212 |
PR212 |
Factroy reset |
| Poles |
3P |
3P |
3P |
3P |
| Rating (A) |
250 |
400/630 |
800 |
1600 |
| 1 |
L |
Overload Current Setting (A) |
(0.4,0.5,0.55,0.6,0.65,0.7,0.75,0.8)xIn |
(0.4,0.5,0.55,0.6,0.65,0.7,0.75,0.8)xIn |
(0.4,0.5,0.55,0.6,0.65,0.7,0.75,0.8)xIn |
(0.4,0.5,0.55,0.6,0.65,0.7,0.75,0.8)xIn |
1.0In |
| 2 |
Time Delay at Overload Current Setting |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S,6S,12S,18S |
3S |
| 3 |
S |
Short - Circuit Current Setting (A) |
(1, 2, 3, 4, 6, 8, 10,OFF)xIn |
(1, 2, 3, 4, 6, 8, 10,OFF)xIn |
(1, 2, 3, 4, 6, 8, 10,OFF)xIn |
(1, 2, 3, 4, 6, 8, 10,OFF)xIn |
6In |
| 4 |
Time Delay at Short Circuit Current Setting |
0.05, 0.1, 0.25, 0.5 |
0.05, 0.1, 0.25, 0.5 |
0.05, 0.1, 0.25, 0.5 |
0.05, 0.1, 0.25, 0.5 |
0.1S |
| 5 |
I |
Instantaneous Current Setting |
(1.5, 2, 4, 6, 8, 10, 12,OFF)xIn |
(1.5, 2, 4, 6, 8, 10, 12,OFF)xIn |
(1.5, 2, 4, 6, 8, 10, 12,OFF)xIn |
(1.5, 2, 4, 6, 8, 10, 12,OFF)xIn |
10In |
| 6 |
G |
Ground Fault Current Setting (A) |
(0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn |
(0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn |
(0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn |
(0.2,0.3,0.4, 0.6,0.8,0.9,1.0, OFF)xIn |
1.0In |
| 7 |
Time Delay at Ground Fault Setting |
0.1, 0.2, 0.4, 0.8 |
0.1, 0.2, 0.4, 0.8 |
0.1, 0.2, 0.4, 0.8 |
0.1, 0.2, 0.4, 0.8 |
0.4S |
| 8 |
|
Selection of electric or electronic parameters set |
Function SET (switch ELT/MAN) |
| 9 |
|
Used for setting parameters of dip switch of zero line |
InN=%In,switch 50/100 |
| 10 |
|
Socket for connection measuring device |
Panel socket |