Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 1.3/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MCB DAB6-63 | |||||||
For protection of general power distribution (IEC/EN 60898-1) | |||||||
Poles | 1P | 2P | 3P | 4P | |||
Electrical performance | |||||||
Functions | short circuit protection,overload protection,isolationg,control | ||||||
Rated frequency f Hz | 50-60Hz | ||||||
Rated working voltage Ue V AC | 230/400 | 400 | |||||
Rated current In A | 6,10,16,20,25,32,40,50,63 | ||||||
Rated insulated voltage Ui V | 500 | ||||||
Impulse withstand voltage Uimp kV | 4 | ||||||
Instantaneous tripping type | DAB6-63N | B/C/D | |||||
DAB6-63H | B/C/D | ||||||
Rated short circuit Icn(kA) | DAB6-63N | 4.5 | |||||
DAB6-63H | 6 | ||||||
Release type | Thermal magnetic type | ||||||
Service life(O~C) | Mechanical | Actual value | 20000 | ||||
Standard value | 4000 | ||||||
Electrical | Actual value | 8000 | |||||
Standard value | 4000 | ||||||
Connection and installation | |||||||
Protection degree | IP20 | ||||||
Wire mm² | 1~35 | ||||||
Working temperature | -5 ~+40ºC | ||||||
Resistance to humidity and heat | Class 2 | ||||||
Altitude above sea | ≤2000 | ||||||
Relative humidity | +20ºC , ≤90% ;+40ºC , ≤50% | ||||||
Pollution degree | 2 | ||||||
Installation environment | Avoid obvious shock and vibration | ||||||
Installation class | Class II, Class III | ||||||
Mounting | DIN35 rail | ||||||
Combination with accessories | |||||||
Auxiliary contact | Yes | ||||||
Alarm contact | Yes | ||||||
Shunt release | Yes | ||||||
Undervoltage release | Yes | ||||||
Auxiliary contact+Alarm contact | Yes | ||||||
Dimensions(mm) (WxHxL) | a | 17.5 | 35 | 52.5 | 70 | ||
b | 80.2 | 80.2 | 80.2 | 80.2 | |||
c | 76.5 | 76.5 | 76.5 | 76.5 |