Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 26/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The DAM1 series circuit breakers are designed for conducting current in normal mode and switching it off in case of short circuits, overload, inadmissible bucking, operational actuation, and tripping of electric circuit parts. They are suitable for use in electric units with an operative voltage limit of 400V and rated current ranging from 12.5 to 1600A.
These circuit breakers comply with the requirements of EN 60947-1 and EN 60947-2.
Thermal Protection Function: The bimetal in the breaker provides thermal protection by bending towards the metal with less extension when heated. This action releases a notch to disable the breaker, with the bending speed proportional to the current passing through it, offering overcurrent protection.
Magnetic Protection Function: The breaker also protects against short circuits by instantly opening to break the system energy in case of a short circuit. This function is fulfilled by a mechanical opening mechanism operating with magnetization from the short circuit current's magnetic area.
For high-quality circuit breakers, trust Shanghai DaDa Electric Co., Ltd.
Thermal-Magnetic fixed type Circuit Breakers | ||||||
Model | DAM1-250 | |||||
Breaking Capacity Code | N | S | H | G | ||
Rated Current of Frame size- Inm (A) | 250A | |||||
Rated Current-In(40,50 or 55ºC) (A) | 63 - 80-100-125 - 160(180) - 200(225) - 250(320)A | |||||
Rated İnsulation Voltage -Ui(a.c.) 50-60Hz (V) | 750V | |||||
Rated operation Voltage -Ue(a.c.) 50-60Hz (V) | 400/415V | |||||
Number of Pole | 3P /4P | |||||
Rated ultimate short Circuit breaking Capacity kA Icu AC400V/50Hz O-CO (KA) | 35 | 50 | 65 | 85 | ||
Rated service short Circuit breaking Capacity kA Ics AC400V/50Hz O-CO-CO (KA) | 26.25 | 37.5 | 48.75 | 51 | ||
Rated short-circuit breaking capacity Icm(peak)/cos ф AC400V/50HZ O-CO (KA) | 77/0.25 | 114/0.25 | 143/0.2 | 178/0.2 | ||
Rated impulse withstand Voltage -Uimp (V) | 8000 | |||||
Dielectric Propery (V) | 3000 | |||||
lonization distance (mm) | ≤30/0 | |||||
Endurance | Total Cycles | 8000 | ||||
Electrical Life | 1000 | |||||
Mechanical Life | 7000 | |||||
Over Current trip | Thermal and Magnetic release fix type | √ | ||||
Category (EN 60947-2/IEC 60947-2) | Main circuit | A/B | ||||
Auxiliary circuit | AC-15 | |||||
Under Voltage Release | √ | |||||
Shunt Release | √ | |||||
Auxiliary Contact | √ | |||||
Alarm Contact | √ | |||||
Auxiliary Contact and Alarm Contact | √ | |||||
Handle Operation Mechanism | √ | |||||
Electrical Operastion Mechanism | √ | |||||
DIN clips | - | |||||
Terminal cover | √ | |||||
Phase seperator | √ | |||||
Extention Handle | - | |||||
W (mm) | 3P | 105 | ||||
4P | 140 | |||||
L (mm) | 3P | 170 | ||||
4P | 170 | |||||
H (mm) | 3P | 103.5 | ||||
4P | 103.5 | |||||
Weight | Fixed version 3P/4P | 2.7/3.5 | 41.5/5.5 | |||
Plug-in version 3P/4P | 3.2/4.2 | 4.6/6 | ||||
Draw out version 3P/4P | 3.6/4.6 | 5/6.4 |